Focus on Containment Systems to Achieve NFPA Compliance


JESSUP, Md., Feb. 21, 2018 /PRNewswire/ -- As a producer of both raised access flooring systems and hot and cold aisle containment solutions, Tate often finds itself faced with questions about fire protection compliance and the role of NFPA 75, Fire Protection of Information Technology Equipment. This data center standard is not only the single most important one for the protection of life and property, but also essential to the prevention of downtime in mission critical facilities. According to Underwriters Laboratories, fire is the least predictable cause of downtime and the one that poses the greatest risk to worker safety.

In many ways, NFPA 75 2013 was drafted to address the significant issues presented by the first containment systems manufactured. Since these systems were developed before any safety standards were established, they quickly became a dreaded topic for local authorities having jurisdiction (AHJ's). This document provided much-needed clarification on the fire safety issues presented by creating unprotected spaces within a protected room, or by creating air plenums where none existed before. The 2017 edition provides even further clarification of the rules set forth in 2013.

When cold aisles are contained with a ceiling, or hot aisles contained by creating a wall above the rack, there is no means for the fire-suppressing agent, either water or gas, to get to the fire. The challenge for manufacturers and code authorities is to define materials and methods that meet the demand for life safety while effectively creating supply and return air segregation to optimize the mechanical system and make it more energy efficient.

What's the strategy? Focus on two essential areas to make sure your containment systems comply with the requirements of NFPA 75.

First, you have to ensure compliance from a materials standpoint. Materials used to create the doors, walls, and partitions of the containment system must meet NFPA requirements. NFPA requires the polycarbonate and plastic materials used in these systems have a flame spread index of 50 or less, and a maximum smoke development of 450 in accordance with either ASTM E84 or UL723. This requirement limits the propagation of flame and creation of smoke should a fire occur.

Second, make sure there is no containment system interference. Doors, walls, and partitions must be incorporated into a framing system that can be tied into ? and released by ? the fire protection early warning system. Whether this is accomplished via pneumatic or electronic controls, the containment system should not interfere with sprinklers or agent in the event of a fire. Pneumatic and electronic release systems ensure that fall-away cold aisle ceilings and hot aisle partitions do not interfere in an emergency situation.

To help you overcome the design challenges involved with containment and NFPA compliance, Tate provides custom engineering and manufacturing for all of our data center containment and structural ceiling systems.

Learn more about Tate Containment.

SOURCE Tate


These press releases may also interest you

at 23:19
The Industrial Technology Research Institute (ITRI) convened the 2024 ITRI Net Zero Day in Taipei, accelerating industry's transition to net-zero emissions. The event highlighted key innovations and successful business cases, focusing on the...

at 22:33
The report titled "Identity Governance & Administration Market by Component (Services, Solution), Modules (Access Certification & Compliance Control, Access Management, Identity Lifecycle Management), Organization Size, Deployment, Vertical - Global...

at 22:03
The report titled "Contract Research Organization Services Market by Type (Clinical Research Services, Consulting Services, Data Management Services), Trial Phase (Phase I, Phase II, Phase III), Therapeutic Area, Molecule Type, End-User - Global...

at 20:35
Bristow Group Inc. , the global leader in innovative and sustainable vertical flight solutions, today announced it will release its first quarter 2024 financial results and selected financial outlook for 2025 and 2026 after market close on Tuesday,...

at 20:25
AIDS Healthcare Foundation applauds the government of Colombia for issuing a compulsory license on HIV drug dolutegravir, which will allow the country to access affordable generic versions of the treatment as an alternative to the costly branded...

at 20:00
SUNRATE, an intelligent global payment and treasury management platform has been named one of the Top 100 Cross-Border Payment Companies for 2024 by FXC Intelligence, which recognises and celebrates the most important players in the cross-border...



News published on and distributed by: